Humidity after heating calculator

Estimate how relative humidity changes when air is heated without adding or removing water vapour.

Heating lowers relative humidity without removing water vapour under this assumption. It does not fix a leak or remove moisture from materials.

Heating lowers relative humidity without removing water vapour under this assumption. It does not fix a leak or remove moisture from materials.

Enter your measurements, then calculate.

Method and limitations

Uses the same Magnus saturation pressure over liquid water as the dew point tool, with a = 17.625, b = 243.04 °C and 6.1094 hPa. T1 and T2 are in °C; RH1 and RH2 are percentages. Both temperatures must be within −40 to 50 °C and T2 ≥ T1. Vapour pressure stays constant. Ventilation, moisture sources, dehumidification and changes in total pressure are excluded. eₛ(T) = 6.1094 × exp(a × T / (b + T)) hPa; RH2 = RH1 × eₛ(T1) / eₛ(T2).

Sources